CPSG Pure Steam Generator
PURE STEAM PRODUCTION FOR PHARMACEUTICAL AND INDUSTRIAL MANUFACTURING
BRAM-COR Pure Steam Generators Mod. CPSG produce dry, saturated steam, suitable for sterilization of pharmaceutical production plants, for direct contact with Active Pharmaceutical Ingredients, for Parenteral and Non-Parenteral dosage form applications. The steam, when condensed, meets USP requirements for Water-for-Injection. The steam is purified using centrifugal and gravity separation methods.

cGMP, ASME and PED standards are baseline criteria in our Pure Steam Generators design and construction: material and instruments are certified and all welds are made by qualified welders.

In detail:
- The evaporation column is designed to minimize steam speed to avoid the entrainment of water droplets, which are separated from the steam by means of a special separator.
- A Double Tube Sheet Heat Exchanger provides heating of pre-treated feed water above the boiling temperature, generating pure steam which expands into the evaporation column. Heating medium in the DTS Heat Exchanger is typically industrial steam at 100 to 120 psig (6 to 8 barg).
- Pure steam pressure is maintained by an electronic control system, modulating the supply steam control valve and monitoring the evaporator feed water.
The system shall be fed with Purified Water and heated and heated using industrial steam, however heating can also be achieved using superheated water or with direct electrical power supply.
Capacities range: from 20 to 8000 kg/h.

BRAM-COR KPSG Kettle Pure Steam Generators, provided with a horizontal evaporation chamber with kettle end, are also available for special space needs in case of high capacities.
HOW CLEAN STEAM / PURE STEAM GENERATOR WORKS

01 – FEED WATER 02 – CLEAN STEAM / PURE STEAM
03 – BLOW-DOWN/DRAIN 04 – INDUSTRIAL STEAM 05 – CHILLED WATER
06 – SAMPLING POINT 07 – PURE STEAM PRESSURE TRANSMITTER
08 – MODULATING VALVE 09 – INDUSTRIAL STEAM PRESSURE SWITCH
10 – SANITARY PUMP 11 – STEAM TRAP 12 – LEVEL PROBE
13 – SAFETY VALVE 14 – PURE STEAM SAMPLING CONDENSER
15 – CONDUCTIVITY METER 16 – DEMISTER